After Burnouts:
1. Remove and properly dispose of used oil and refrigerant, and replace burned out compressor.
2. Determine system’s oil capacity.
3. Determine the required amount of Rx-Acid Scavenger using the dosage chart on the enclosed detailed instructions.
4. Add Rx-Acid Scavenger to system as directed by adding the product directly into the compressor of an opened system or injected directly by using the Universal Treatment Injector (P/N 4779-0). Return system to service.
System Maintenance
1. Use the Nu-Calgon Phase III® Acid Test Kit to verify acid contamination.
2. Establish system’s oil capacity.
3. Determine the required amount of Rx-Acid Scavenger using the dosage chart inside the box
4. Add Rx-Acid Scavenger to system as directed.
5. Return system to service. (NOTE: it is always recommended that driers be changed.)