The industry standard for flushing refrigeration and air conditioning systems
Ideal for system clean-up after burnouts
Cleaning is fast, efficient and verifiable
Flush line sets for R-410A or A2L conversions
A2L Ready
Rx11-flush® is designed to quickly and easily flush contaminants from air conditioning and refrigeration systems and line sets. It is ideal for flushing after a compressor burnout, during a refrigerant retrofit, or at a new system installation. Formulated as a unique solvent, Rx11-flush is an azeotropic cleaner that is fast acting, fast evaporating, compatible with system components, nonflammable and noncorrosive.
This product must be used in accordance to the following directions by HVACR professionals only.
One canister will flush a 3-4 ton system or 1-2 line sets (four 35´lines), but the amount will vary depending on line configuration and contamination level. Inject Rx11-flush into the system using below guide:
Up to 1/2˝ tubing: Use a 20-30 second burst of Rx11-flush through each line for every 50 feet.
Up to 7/8˝ tubing: Use a 60-90 second burst of Rx11-flush through each line for every 50 feet.
Either inject additional Rx11-flush or make required repairs. Pull vacuum to boil off any remaining flush.
ADDITIONAL TIPS:
1. If any flush remains in canister, it can be saved for future flushing. Simply turn Injection Valve fully counterclockwise and remove from canister. If local regulations permit, recycle this canister.
2. For extra protection, charge system with Rx-Acid Scavenger® (4301-02) as insurance to protect against acid contamination.
3. See application bulletin 3-112 for additional details. Use only the appropriate refrigerant, proper recovery equipment, component parts, tools and lubricants as established in the industry and as listed in this service bulletin.